Sinotimer Mc101 Manual «4K 2024»
Connect the resistor element between Terminals 8 and 9 , with the third "extra" wire going to Terminal 10 . Control Output:
Set "AT" to 1. The AT light on the panel will blink until the cycle is complete and the controller has calculated its PID constants.
Hold the (or SET + <) keys for 3 seconds to enter the menu. Use the arrows to find the "Unit" parameter. Change the value from 000 (Celsius) to 001 (Fahrenheit). Hold the MODE key for 3 seconds to exit and save. Entering PID Auto-Tuning: sinotimer mc101 manual
Ensure the thermocouple type set in the software matches the physical sensor connected to avoid incorrect readings.
For optimal control, you can trigger the function. Access the internal menu and locate the "AT" parameter. Connect the resistor element between Terminals 8 and
If using an SSR to control a high-current load, always attach a heat sink to prevent the relay from overheating.
Connect the AC power supply to Terminals 1 and 2 (typically 120V/240V L and N). Sensor Connection: Hold the (or SET + Ensure the thermocouple
Sinotimer devices are built to resist dust and moisture, but they should still be housed in a proper enclosure for longevity in harsh environments. Temperature Controller - Sinotimer